Central or decentral heat-recovery ventilation: which one for a house

A 150 m² house with 4 people and 11 rooms needs 120 m³/h of fresh air. One central unit with ducts does that with a single machine, 9 air valves and 2 holes through the facade: the air comes into the living room and bedrooms, passes through the hall and leaves through the kitchen and bathrooms. With wall units, each room is ventilated on its own: 10 units in pairs (or 9 with two fans), 20–25 m³/h each, exchanging 210 m³/h between them, because a bedroom’s air no longer reaches the bathroom. In Bucharest, ventilation loses 265 kWh of heat a year with the central unit (91 %) and 772 kWh–1,287 kWh with wall units (85 % certified, 75 % in use); electricity: 319 kWh against 442 kWh; filters: 2 changes a year against 18; installed cost: €6,540 against €5,610–14,950 (). Semper Supra designs central systems and recommends them for new houses and deep retrofits; wall units make sense for one or two rooms of an existing home where ducts cannot go. Below: the calculation for your house, the comparison criterion by criterion, the PHI-certified wall units and the FAQ.

Calculator · air flow · wall units · cost

How many wall units would your house need?

Nominal air flow120 m³/h4 people × 30 or 0.30 h⁻¹ × 375 m³
Wall units10 or 9in pairs or with two fans, 20–25 m³/h each
Heat lost a year265 kWh vs 772–1,287 kWhcentral vs wall units (laboratory–in use)
Installed cost€6,540 vs €5,610–14,950wall: 10 units × €560–1,500
The comparison for the house you chose
CentralDecentral
Fresh air exchanged120 m³/h210 m³/h
Units1 unit, 9 air valves10 in pairs or 9 with two fans
Holes through the outside wall210 or 9, Ø 160–200 mm
Filter changes a year2, at one unit18 (9 units × 2)
Heat lost through ventilation265 kWh772 (laboratory) – 1,287 kWh (in use)
Electricity: fans and frost319 kWh442 kWh
Installed cost€6,540€5,610–14,950
Cost a year: heat, electricity, filters€187€360 (laboratory) – €397 (in use)

Units per room: living room: 2 × 22.5, 3 bedrooms: 1 × 25 each, kitchen: 2 × 20, 2 bathrooms: 1 × 25 each. No unit: the technical room and the store room (30 m³/h of extract that the central option does remove).

Enter the floor area, how many people live there, how many bedrooms and bathrooms the house has, and the city. The air flow comes from the ventilation calculator’s room sheet (30 m³/h per person, at least 0.30 air changes an hour); the kitchen is always included. The central option uses a Zehnder ComfoAir Q350 HRV; the decentral one the PHI values of a certified wall unit with at most 25 m³/h per unit, once as in the laboratory and once with 10 points less heat recovery, as is lost in use.

Principle · one unit or a unit in every room

How each works

Both are balanced mechanical ventilation with heat recovery: stale air goes out, fresh air comes in, and a heat exchanger passes the heat from one to the other without mixing them. The difference is where the exchanger sits and how the air reaches the rooms.

Central: one unit in the plant room, ducts, 2 holes through the facade
bedroombedroombathplantlivinghallkitchen
Decentral: units in the outside walls, no ducts
bedroombedroombathplantlivinghallkitchen
supply airextract airhole through the facadewall unit

Schematic of one storey, not to scale. The page’s 150 m² house has two storeys, three bedrooms and two bathrooms.

Central heat recovery ventilation: how it works

A single unit (an HRV, or an ERV with moisture recovery) sits in a plant room, in the loft or above a suspended ceiling. Two ducts link it to the outside through two holes in the facade or the roof: fresh air and exhaust air. Inside, one duct network brings fresh air, filtered and warmed by the exchanger, to the living room, bedrooms and study, and another takes it out of the kitchen, bathrooms and store room. In between, the air moves through the hall, under the doors. Each room gets what it needs, set at the valves when the system is commissioned.

Wall-mounted heat recovery unit: how it works

A decentral unit sits in a hole through the outside wall of the room it ventilates, with no ducts. There are two kinds. A two-fan unit has a continuous exchanger inside (counter-flow, sometimes with a membrane that also recovers moisture): air comes in and goes out at the same time, like a small central unit. All five decentral units certified by the Passive House Institute on 31 October 2026 are of this kind.

Push-pull heat recovery units in pairs: how they work

An alternating (push-pull) unit has one reversible fan and a ceramic block. For about a minute it blows warm room air out and the ceramic warms up; then the fan reverses and cold outdoor air comes in through the warm ceramic, cooling it. To keep the flow balanced the units work in pairs: while one blows out, the other blows in, even when they sit in different rooms. They usually have axial fans, which a small pressure difference can stop.

Air flows · 150 m², 4 people

Air flows and distribution

The air flow is worked out the same way for both, with the Passive House Institute method of the ventilation calculator: 30 m³/h per person, at least 0.30 air changes an hour, rounded up to 10 m³/h. For the 150 m² house that is 120 m³/h (0.32 h⁻¹). What differs is how the air reaches the rooms.

Room by room with central ventilation

Fresh air is shared between the living rooms (the living room 45 m³/h, each bedroom 25 m³/h), passes through the halls and leaves from the wet rooms (the kitchen 40 m³/h, each bathroom 25 m³/h, the plant room and store room 15 m³/h each). The same air serves twice: first in the bedroom, then in the bathroom. That is why 120 m³/h is enough for the whole house.

How many wall-mounted heat recovery units do I need

A wall unit ventilates only the room it sits in, and takes out as much as it brings in. The page’s rule: every living room gets its supply flow, the kitchen, bathrooms and WC their extract flow, with at most 25 m³/h per unit (the continuous range of the certified unit used in the calculation). For the 150 m² house: living room: 2 × 22.5 m³/h, 3 bedrooms: 1 × 25 m³/h each, kitchen: 2 × 20 m³/h, 2 bathrooms: 1 × 25 m³/h each, that is 9 two-fan units or, rounded to pairs, 10 alternating units. Between them they exchange 210 m³/h with the outside, 90 m³/h more than the central unit, because air no longer passes from one room to the next. The plant room and the store room get no unit (30 m³/h of extract missing).

Heat recovery ventilation without ducts: transfer air

Without ducts there is no controlled path through the house. Each unit works on its own facade, and the wind and the temperature difference between low and high (the stack effect) press differently on each wall; closed doors separate the rooms. The EwWalt project (RWTH Aachen, HLK Stuttgart, ITG Dresden) showed that alternating units placed on different facades, “across corners”, see large pressure differences between them (REHVA Journal 4/2019). Bathrooms without a window or an outside wall cannot take a unit and stay on a simple extract fan with no recovery.

Recovery · PHI · field studies · Bucharest

Heat recovery in practice

The Passive House Institute certifies central units with 79–94 % heat recovery (the ventilation calculator’s list) and decentral units with 78–86 % (PHI database). Certification figures are measured in a laboratory, with balanced flows and no wind.

What is lost in use: wind, imbalance, stack effect

A wall unit has no ductwork to shield it from the pressure on the facade. Filis, Kolarik and Smith (Energy and Buildings, 2021) simulated a full year: wind alone reduces heat recovery by up to 8 % in units with centrifugal fans and up to 22 % in units with axial fans; with the stack effect, up to 20 % and 52 %. The same paper cites field measurements on 60 room units (Merzkirch et al.): imbalances of up to 60 % from wind or stack effect and average heat recovery about 8–22 % below the manufacturers’ values, but also fans using less than 0.25 Wh/m³, about half of the central units measured. In alternating units, the effective mean flow was about 85 % of the flow in continuous operation, and in strong wind at low speed it can fall to zero (EwWalt). We could not read the Merzkirch field study itself; its figures are as cited by Filis et al.

Heat lost a year, Bucharest

For the comparison: the central Zehnder ComfoAir Q350 HRV with 91 %, at 120 m³/h; wall units with 85 % (Zehnder ComfoAir 70, the best efficiency ratio on the PHI list) at 210 m³/h, once as in the laboratory and once with 10 points less, the page’s assumption for real use, within the range of the studies above. With 74.3 kKh to 23 °C, central ventilation without recovery would lose 2,942 kWh a year; with it, 265 kWh. The wall units lose 772 kWh in laboratory conditions and 1,287 kWh in use: 2.9–4.9 times as much, mainly because they move 210 m³/h instead of 120 m³/h.

Table · PHI database · 31 October 2026

Passive House certified wall units

All single-room decentral units in the Passive House Institute database, read on 31 October 2026, with their certificate values. No prices; we do not recommend a particular manufacturer.

UnitContinuous flow, m³/hHeat recoveryElectricity, Wh/m³Moisture recoveryNoise (certificate)Frost (certificate)PHI certificate
Zehnder ComfoAir 7015–2585 %0.2464 %≤ 30 dB(A) in a secondary room up to 25 m³/hreduces supply from −8.2 °C, stops it at about −13 °C0826vs03
Zehnder ComfoSpot 5015–2580 %0.3054 %≤ 30 dB(A) in a secondary room up to 25 m³/hreduces supply from −8.8 °C, stops it at about −13 °C1195vs03
bluMartin freeAir 100e ERV20–5086 %0.3661 %≤ 25 dB(A) at 50 m³/h with the Premium cover; 34 dB(A) with the standard onebypass and balanced flow reduction from −9 °C2537vs03
Vaventis fresh-r20–3078 %0.28—24 dB(A) at 30 m³/h, 29 dB(A) at 40 m³/hexternal 600 W pre-heater from −4 °C0827vs03
Meltem M-WRG-II E10–5078 %0.3855 %≤ 25 dB(A) up to 50 m³/h (U2 mounting with ducts)unbalances the flows from about −9.5 °C1328vs03

Continuous flow is the range in which the unit meets the noise limit; above it the unit runs only as a boost setting. Values are for the installation variant in the certificate. All five have a continuous exchanger and two fans; no alternating unit with a ceramic block was on the list.

Noise · 25 dB(A) in rooms

Noise

Wall-mounted heat recovery unit noise

The Passive House Institute asks for at most 25 dB(A) in living rooms and 35 dB(A) in the plant room. With central ventilation the fans sit in the plant room and the duct silencers keep the noise away from the bedrooms. With a wall unit the fan is in the room. The certified units meet the limit only in their continuous range: for example, at 50 m³/h one unit gives 25 dB(A) with its best cover and 34 dB(A) with the standard one, and another passes 25 dB(A) above 30 m³/h (the certificates in the table). That is why the page’s calculation does not load a unit with more than 25 m³/h. For uncertified units there are no comparable measurements. One more thing: a Ø 160–200 mm hole through the wall with a unit in it lets in more outdoor noise than a solid wall.

Filters · maintenance

Filters and maintenance

Filters: how many and which class

The PHI certificates ask for a fine ePM1 50 % (F7) filter on the outdoor air, which stops pollen and much of the fine dust, and at least ISO Coarse 60 % (G4) on the extract air, which protects the exchanger from dust. A central system has two filters in one place; the 150 m² house with wall units has 9 units, each with its own filters, in different rooms, some under the ceiling. Many uncertified units have coarse filters only.

Time and money a year

The page’s assumption (indicative prices, ): filters are changed twice a year; a set for the central unit costs €47 and takes about 15 minutes, a set for a wall unit €11 and about 10 minutes, plus washing the ceramic block of alternating units. A year: 2 changes, €93 and half an hour for the central system; 18 changes, €202 and about 3 hours with wall units. Central ductwork is checked and, if needed, cleaned every few years.

Frost · humidity · Bucharest

Frost and humidity

Heat recovery unit in winter: frost

In cold weather the moisture in the extract air can freeze in the exchanger. The central unit has an electric pre-heater that starts below −1.5 °C (the PHI switch-on point): in Bucharest, 482 hours a year and 67 kWh of electricity, and the flows stay balanced. Certified wall units generally have no pre-heater: they protect themselves by unbalancing the flows or stopping the supply air. The certificates say how: one reduces the supply air from −8.2 °C and stops it at about −13 °C, another reduces the flow from −9 °C, another unbalances from −9.5 °C, and one has an external 600 W pre-heater from −4 °C. Bucharest has 64 hours a year below −8 °C and 17 below −13 °C, and its design temperature is −15 °C (SR 1907-1). In those hours the house gets less fresh air, or colder air, and the missing air comes in through leaks.

Humidity and condensation

Moisture recovery (ERV) exists for both: four of the five certified wall units also recover moisture, 54–64 %. PHI writes on the same certificates that in cool temperate climates moisture recovery should only be used where the house produces little moisture, and that above 60 % humidity-controlled flow is needed. What that means for a house in Romania is on the page on relative and absolute humidity and in the HRV or ERV lesson of the ventilation calculator. A wall unit drains what condensate it has to the outside through the facade cover (as one of the certificates says).

Facade · airtightness · thermal bridges

Holes in the facade, airtightness, thermal bridges

How many holes through the insulated wall

The central option has 2 penetrations of the envelope, usually together next to the unit: fresh air and exhaust. Wall units need 10 (or 9) core-drilled holes of Ø 160–200 mm through the insulated wall, one per unit, on every facade. Each has to be sealed to the airtight layer inside and to the insulation outside, and each is a small point thermal bridge.

Airtightness of a Passive House

A Passive House has n50 ≤ 0.6 h⁻¹ in the pressure test: all air that passes through a leaky hole does so without heat recovery. Each extra penetration is one more detail to build well and one more chance that it is not. We give no figure for how much one hole leaks; only that ten sealing details spread over the facades are harder to make and check than two. On thermal bridges and mould: the page on thermal bridges and mould.

Cost ·

Cost

The central unit with ducts and installation for the 150 m² house: €2,620 + €2,240 + €1,680 = €6,540 (the ventilation calculator’s figures; market guides give €4,670–6,540 for a new house). One installed wall unit costs €560–1,500 (Onninen guide); 10 units: €5,610–14,950. A year: the lost heat at €0.071/kWh (gas at €0.065/kWh, a 92 % boiler), electricity at €0.234/kWh, and the filters.

CentralWall units, 85 %Wall units, 75 % in use
Purchase and installation€6,540€5,610–14,950€5,610–14,950
Heat lost through ventilation, a year265 kWh · €19772 kWh · €551,287 kWh · €92
Electricity, a year319 kWh · €75442 kWh · €103442 kWh · €103
Filters, a year2 × €47 = €9318 × €11 = €202€202
Total a year€187€360€397

Prices with VAT, indicative, not quotes. Wall units need no plant room and no suspended ceilings for ducts, which can matter in a retrofit; a new house includes the duct routes anyway. Prices converted from lei at the BNR reference rate of 28 October 2026, 1 € = 5.3495 lei, and rounded.

Table · at a glance

Side by side

CriterionCentralDecentral
Units1 unit, 9 air valves10 in pairs or 9 with two fans
Air exchanged120 m³/h210 m³/h
Distributioncontrolled through the house, from living rooms to wet roomseach room on its own; no air passes between rooms
Recovery (PHI)79–94 %; here 91 %78–86 %; ~8–22 % less in use
Heat lost a year265 kWh772 kWh–1,287 kWh
Electricity a year319 kWh442 kWh
Noisefans in the plant room, silencersthe fan in the room; ≤ 25 dB(A) only in the continuous range
Filters2 changes a year, one place18 changes a year, 9 places
Frostpre-heater, 482 h a yearimbalance or stop below −8…−13 °C
Holes through the facade210 or 9
Spaceplant room or loft, ductsnone; free outside walls only
Installationdesign, ducts, best during constructionroom by room, also in an occupied home
Installed cost€6,540€5,610–14,950
Recommendation · new houses · retrofits · flats

When each makes sense

Central or decentral ventilation: when to choose which

Central for new houses, deep retrofits, Passive House and nZEB: flows are designed room by room, air moves through the house from living rooms to wet rooms, recovery stays as measured, and filters, noise and frost are dealt with in one place. Decentral for one or two rooms of an existing home, for a flat where no ducts can go, or as a first step before a larger retrofit. There a certified wall unit within its continuous range is far better than an open window in winter; PHI itself, in the description of the list, calls them “particularly suitable for renovation projects”, and for small homes.

What Semper Supra recommends

We design central systems and do not install wall units; the reader should know that when reading the recommendation. For a whole house we recommend the central option for the reasons on this page: for the 150 m² house it loses 2.9–4.9 times less heat, has 2 filter changes a year instead of 18, 2 holes in the facade instead of 10, and keeps the flows balanced at −15 °C, at a cost close to the middle of the decentral range. If your home is one where ducts do not fit, a certified wall unit is a good choice, not a second-rate one. Flows and the unit for your house: the ventilation calculator; the design: Semper Supra’s services.

Frequently asked questions

Central or decentral ventilation, in short

Central or decentral ventilation: which should I choose?

For a whole house, new or deeply retrofitted, central: one unit, 9 air valves and 2 holes in the facade for a 150 m² house, with 265 kWh of heat lost a year in Bucharest. Decentral for one or two rooms, or where ducts do not fit.

Are wall-mounted heat recovery units worth it?

In a room with no other ventilation, a PHI-certified unit within its continuous range (15–50 m³/h depending on the model) is worth it compared with an open window in winter. For a whole house the 10 units cost €5,610–14,950 installed and lose 2.9–4.9 times as much heat as a central unit costing €6,540.

How many wall-mounted heat recovery units do I need?

One in every living room, in the kitchen and in every bathroom, plus one more where the room’s flow exceeds 25 m³/h. For a 150 m² house with 4 people: 9 two-fan units or 10 alternating ones (in pairs). The calculation for your house is on this page.

How do push-pull heat recovery units work?

Each unit has a reversible fan and a ceramic block. For about a minute it blows warm air out and heats the ceramic, then it draws cold outdoor air in through the warm ceramic. Two units run in opposite phase so the flow of the house stays balanced.

Is there heat recovery ventilation without ducts?

Yes: decentral wall units. They have no ducts, but each ventilates only the room it is in, so a house needs many (9–10 for 150 m²) and exchanges more air with the outside (210 m³/h against 120 m³/h).

How loud is a wall-mounted heat recovery unit?

PHI-certified units meet 25 dB(A) in a living room only within their continuous range, usually 20–30 m³/h, some up to 50 m³/h. On boost they exceed 30–40 dB(A). The fan is in the room; with central ventilation it sits in the plant room.

Does a heat recovery unit freeze in winter?

The exchanger can freeze below about −1.5 to −9 °C, depending on the type. The central unit starts a pre-heater (482 hours a year in Bucharest); certified wall units reduce or stop the supply air, some at about −13 °C, above Bucharest’s design temperature of −15 °C.

Method · updated on

Method and sources

The same model as the ventilation calculator (hour-by-hour balance on the PVGIS typical year, 23 °C indoors in winter), for two versions of the same house.

  1. Air flow

    Nominal = max(people × 30, 0.30 × volume), rounded up to 10 m³/h; supply shared by the living rooms (living 2, others 1), extract by the reference flows (kitchen 60, bathroom 40, WC, store, plant room 20), in steps of 5 m³/h.

    Source: Passipedia · PHI

  2. Wall units

    Every living room, the kitchen, the bathrooms and the WC get ceil(flow / 25) units; alternating units are rounded up to an even number. Air exchanged = the sum of the room flows.

    Source: the calculator’s room sheet

  3. Heat lost

    Q = (1 − ηHR) · 0.33 · V̇ · Gt, with Gt the degree hours to 23 °C on the days with a mean below 12 °C, month by month.

    Source: PVGIS

  4. Electricity

    Fans: Pel · V̇ · 8,760 h (0.24 and 0.24 Wh/m³); a pre-heater for the central unit below −1.5 °C; wall units without a pre-heater.

    Source: PHI certificates

  5. In use

    Wall-unit heat recovery minus 10 points: an assumption, within the studies’ 8–22 %.

    Source: Filis et al., 2021 · EwWalt, 2019

Checks

CheckReferenceThis page
Air flow of the 150 m² houseventilation calculator: 120 m³/h120 m³/h
Heat kept by the Q350 HRVventilation calculator: 2,677 kWh2,677 kWh
Units per roomΣ flows = 210 m³/h9 · 10

Limits

  • Simplified balance: no infiltration, no hour-by-hour imbalance; the loss in use is one assumption for the whole year.
  • The air missing from the plant room and the store room in the decentral option is not counted, nor the simple extract fans some people put there.
  • Standby power of wall units (0–3.8 W per unit in the certificates) is not counted.
  • Filter prices and change times are indicative assumptions; system prices come from market guides, not quotes.
  • We found no field study for Romania; the field figures are from Germany and Denmark.

Sources

  • Passive House Institute, component database: single-room decentral units, with their certificates (read on 31 October 2026)
  • Passive House Institute, ventilation units (the ventilation calculator’s list) · PHI criteria for ventilation units
  • V. Filis, J. Kolarik, K. M. Smith (2021), The impact of wind pressure and stack effect on the performance of room ventilation units with heat recovery, Energy and Buildings 234; abstract and introduction, including its citation of Merzkirch et al. (2016)
  • T. Hartmann et al. (2019), Ventilation efficiency of decentralized alternating residential ventilation units, REHVA Journal 4/2019 (the EwWalt project)
  • Passipedia, air volumes · Onninen and RoVento, prices, October 2026
  • Climate data: PVGIS typical meteorological year 2005–2023, hourly · SR 1907-1, design outdoor temperatures

Calculation and text: SEMPER SUPRA INITIATIVE S.R.L. · Climate data: PVGIS © European Union, 2001–2026.