Semper Supra · calculator · heat recovery ventilation

Heat recovery ventilation calculator: room air flows, HRV or ERV, savings

The room-by-room air-flow sheet of the Passive House Institute method (the same as the PHPP protocol), a choice of 31 units with their certified figures, then what you gain: heat kept, electricity used, supply-air temperature, winter humidity, cost and payback. Every figure can be changed.

For a 150 m² house with 4 persons in Bucharest: nominal flow 120 m³/h (0.32 air changes per hour); a 91 % heat-recovery unit keeps 2,677 kWh of heat a year of the 2,942 kWh you would lose by airing, that is 114 € a year with gas heating, after the fan electricity. Below, the sheet for your house.

Nominal air flow——
Heat kept per year——
Saving per year——
Ventilation design sheet · PHI method
Part 1 · design sheet

Air flows room by room

The rooms are generated from the house data; change the name, type, level, area or height, add or delete rooms. Supply rooms get fresh air, extract rooms take it out, halls let it pass.

    Part 2 · the unit

    The ventilation unit and its requirements

    Semper Supra calculator · sempersupra.ro/en/heat-recovery-ventilation-calculator/ · a guide, not a substitute for the design.

    Part 3 · result

    Heat, electricity, humidity and cost for the chosen unit

    Indoor relative humidity, month by month: 23 °C in winter, 24 °C in summer with air conditioning

    —

    What this calculation does not tell you

    Steady-state balances after the PHI method, simplified: heat over the hours of the heating season, humidity as a monthly mean, the frost pre-heater as an electric heater. It does not calculate duct pressure losses, noise or duct sizes. Prices are guides (October 2026), not quotes. It does not replace the building-services design or a PHPP model.

    Result · 150 m², Bucharest, Zehnder ComfoAir Q350

    What heat recovery ventilation gains you in Bucharest

    For the 150 m² house with 4 persons and 120 m³/h: without recovery, the air exchanged would carry 2,942 kWh of heat outside over the heating season (19.6 kWh/m²; PHI gives 20–30 kWh/m² for a normally ventilated home). The Zehnder ComfoAir Q350 HRV (HRV, 91 %) keeps 2,677 kWh and leaves only 1.8 kWh/m² (PHI: 2–7). The fans use 252 kWh a year, frost protection 67 kWh. The net saving with gas at 0.065 €/kWh and a 92 % boiler is 114 € a year.

    HRV · Zehnder ComfoAir Q350 HRVERV · Zehnder ComfoAir Q350 ERV
    Nominal flow · air change120 m³/h · 0.32 h⁻¹120 m³/h · 0.32 h⁻¹
    Without recovery you would lose2,942 kWh/yr2,942 kWh/yr
    Heat kept2,677 kWh/yr2,524 kWh/yr
    Remaining loss, per m²1.8 kWh/(m²·a)2.8 kWh/(m²·a)
    Fan electricity252 kWh/yr364 kWh/yr
    Frost-protection electricity67 kWh/yr · 482 h14 kWh/yr · 64 h
    Supply air at −15 °C19.6 °C20.0 °C
    Humidity in January (23 °C indoors)34 % RH55 % RH
    Highest winter flow (humidity control)120 m³/h270 m³/h · +182 kWh
    Water condensed by the air conditioning in summer1,325 litres1,045 litres
    Saving per year (gas boiler)114 €90 €
    Simple payback57 years73 years

    Continuous operation, 8,760 hours a year, at the nominal flow (the ERV raises it in winter to stay below 55 % RH). Indoors: 23 °C in winter, 24 °C and 50 % RH in summer with air conditioning. Heating season: 4,128 hours of the days with a mean below 12 °C, 74.3 kKh to 23 °C. Moisture produced indoors: 330 g/h. October 2026 prices: gas 0.065, electricity 0.234 €/kWh; system 6,540 €. Prices converted from lei at the BNR reference rate of 28 October 2026, 1 € = 5.3495 lei, and rounded.

    Air flows · 150 m² house, 4 persons

    Air flow: for the house and room by room

    How many m³/h of air do I need?

    The Passive House Institute method starts from the people: 30 m³/h of fresh air per person. For 4 persons that is 120 m³/h. The second criterion is the volume: at least 0.30 air changes per hour, 0.30 × 375.0 m³ = 112.5 m³/h. The nominal flow is the larger of the two, rounded up to 10: 120 m³/h, 0.32 air changes per hour. The unit's base level (92 m³/h) and boost level (156 m³/h) are the nominal divided and multiplied by 1.3, as in PHPP. Above 0.50 air changes per hour the house is over-ventilated and the air dries out in winter.

    Ventilation air flow per room

    Fresh air enters the living room and bedrooms (supply rooms), passes the halls and leaves through the kitchen, bathrooms, WC and store room (extract rooms). The living room gets twice a bedroom's share. For extract, the PHI starting values are kitchen 60, bathroom 40, WC and store room 20 m³/h; here they add up to 180 m³/h, more than the nominal flow, so every extract room is scaled down by the same factor, rounded to 5 m³/h, until extract matches supply exactly. The table below is the sheet of the 150 m² house; in the calculator you can change it room by room and print it.

    RoomRolem²m³Supply, m³/hExtract, m³/hTransfer, m³/hAir change, h⁻¹
    Living roomsupply36.290.545——0.50
    Ground-floor halltransfer12.431.0——451.45
    Kitchenextract15.538.8—40—1.03
    Ground-floor bathroomextract5.213.0—25—1.92
    Plant roomextract8.320.8—15—0.72
    Upstairs bathroomextract8.320.8—25—1.20
    Bedroom 1supply18.646.525——0.54
    Bedroom 2supply14.536.325——0.69
    Bedroom 3supply14.536.325——0.69
    Upstairs landingtransfer12.431.0——752.42
    Store roomextract4.110.3—15—1.46
    Total150.0375.01201200.32
    Example · single-storey house, 120 m²

    Example: heat recovery ventilation in a 120 m² single-storey house

    For a 120 m² single-storey house with 3 persons (300 m³), the nominal flow is 90 m³/h, 0.30 air changes per hour. Fresh air goes into the living room (45 m³/h) and the two bedrooms (25 and 20 m³/h); stale air is extracted from the kitchen (45), bathroom (30) and pantry (15 m³/h). The HRV sits in the attic above the hall, in the middle of the house; outdoor air and exhaust go straight up through the north roof slope, 3.2 m apart.

    Heat-recovery ventilation in a 120 m² single-storey house: plan and section Plan and section: the HRV in the attic above the hall, supply to the living room and both bedrooms, extract from kitchen, bathroom and pantry, every vent on the far side of its room from the door, outdoor air and exhaust straight up through the north roof slope, 3.2 m apart. Supply (fresh, warmed air) Extract (stale air) Outdoor air in Exhaust out Air passing under a door Ceiling vent (valve) Door and its swing Roof terminal HRV in the attic 1 2 3 4 5 6 7 45 m³/h 15 m³/h 30 m³/h 20 m³/h 45 m³/h 25 m³/h outdoor air in exhaust out ridge Outdoor air in and exhaust out go straight up from the unit through the north roof slope: the shortest possible outdoor ducts, with the two roof terminals 3.2 m apart (at least 3 m) so exhaust air is not drawn back in. N 12 m 10 m No. Room Area Supply Extract 1 Kitchen 14 m² — 45 m³/h 2 Pantry 5 m² — 15 m³/h 3 Bathroom 8 m² — 30 m³/h 4 Bedroom 2 13 m² 20 m³/h — 5 Hall 28 m² transfer 90 m³/h — 6 Living / dining 36 m² 45 m³/h — 7 Bedroom 1 16 m² 25 m³/h — Total 120 m² 90 m³/h 90 m³/h 3 persons, 300 m³ → 90 m³/h (0.30 h⁻¹), base 69, boost 117 m³/h. Each vent sits on the far side of its room from the door, so the air crosses the whole room on its way to the door gap. Room sizes illustrative. HRV Bathroom extract valve, far from the door Hall Living supply valve, far from the door ducts in the attic ceiling insulation outdoor air in exhaust out straight up, north slope N S Section A–A through the hall, looking west · the 3.2 m spacing runs along the ridge (see plan)
    Plan and section: the HRV in the attic, supply vents (blue) and extract vents (orange) on the far side of each room from its door, air passing under the doors through the hall, the roof terminals.

    Where to install the HRV unit in a single-storey house

    In the middle of the house, in the attic above the hall. From there the ducts to every room are short and of similar length: low pressure losses, fans that use little power and flows that are easy to balance. If the attic is cold (outside the insulation), the unit and the attic ducts are insulated; the outdoor-air and exhaust ducts, which are cold in winter, get vapour-tight insulation so they do not condense. Leave room next to the unit for changing the filters.

    Where to place supply and extract vents in the rooms

    Supply vents go in the living room and bedrooms, extract vents in the kitchen, bathroom and pantry. Each vent sits on the far side of its room from the door: fresh air crosses the whole room on its way to the gap under the door, and stale air is taken from the far corner of the wet room. In the kitchen the extract vent is near the hob, in the bathroom near the shower.

    How air moves from room to room (transfer air)

    Under the doors. The hall has no vent at all: the 90 m³/h pass through it, from the living room and bedrooms to the kitchen, bathroom and pantry. Doors get a gap of about 1 cm at the bottom or a transfer grille, so the air flows with the doors closed.

    HRV intake and exhaust: where they go and how far apart

    Straight up from the unit through the north roof slope, with the roof terminals 3.2 m apart (at least 3 m). The outdoor ducts carry cold air through the warm part of the house, so they are kept as short as possible: every extra metre means lost heat and a condensation risk. The spacing keeps exhaust air from being drawn back in, and on the north side the fresh air is out of the sun and cooler in summer.

    Air flow per room for a 120 m² house

    With the calculator's rules (30 m³/h per person, at least 0.30 air changes per hour): 90 m³/h in total, shared as in the table below. The extract starting values (kitchen 60, bathroom 40, pantry 20 m³/h) add up to 120 m³/h, above the nominal flow, so they are scaled down by the same factor to 45, 30 and 15 m³/h. The unit's base level is 69 m³/h, its boost level 117 m³/h.

    RoomArea, m²Supply, m³/hExtract, m³/h
    1 · Kitchen14—45
    2 · Pantry5—15
    3 · Bathroom8—30
    4 · Bedroom 21320—
    5 · Hall28transfer 90—
    6 · Living / dining3645—
    7 · Bedroom 11625—
    Total1209090
    HRV or ERV · humidity · frost

    HRV or ERV, dry winter air and frost protection

    HRV or ERV (energy recovery ventilator)?

    An HRV (plain heat exchanger) recovers heat only; an ERV (enthalpy exchanger with a membrane) also recovers moisture: 78 % for the Zehnder ComfoAir Q350 ERV, per PHI. The ERV is often sold as the “better” option that cures dry air. In Romania's climate, for a normally occupied house, the figures say otherwise: in winter the moisture it returns has to be removed with a higher flow (extra electricity and heat loss); in summer it saves the air conditioning a little condensing. For the 150 m² house in Bucharest the HRV saves 114 € a year, the ERV 90 €. An ERV makes sense where the air really gets dry: few people in a large house, or a very cold climate. The Passive House Institute says the same on its ERV certificates: in cool temperate climates, moisture recovery should only be used where the house produces little moisture.

    Dry air in winter: humidity with and without moisture recovery

    Cold outdoor air holds little water: in January in Bucharest, 3.6 g per kg of air, even though its relative humidity is high. Warmed to 23 °C, the same air would have only 21 % RH. The house adds water (people, cooking, showers, plants; PHI counts 330 g/h for 4 persons) and the ventilation removes it. With an HRV and 120 m³/h, the monthly balance gives 34 % RH in January at 23 °C: above the 30 % RH floor below which air feels dry. An ERV with 78 % recovery would return so much water that, at the same flow, the air would pass 80 % RH. That is why PHI requires units with more than 60 % moisture recovery to raise their flow when indoor humidity rises, holding the extract air at 55 % RH. The calculation does the same: the Zehnder ComfoAir Q350 ERV holds 55 % RH in January, but in 5 months the flow rises to 270 m³/h, with 182 kWh of extra heat loss and 112 kWh of extra fan electricity. If the air does get too dry, the PHI remedy, before a humidifier or an ERV, is to lower the flow towards 20 m³/h per person.

    ERV in summer, with air conditioning

    In summer the outdoor air is humid (10.4 g/kg in July in Bucharest). The air conditioning holds the house at 24 °C and 50 % RH (9.3 g/kg) and condenses the excess water: with an HRV, 1,325 litres over the season, up to 15.0 l a day. This is where an ERV helps: it keeps part of the fresh air's water out, and the air conditioning condenses 1,045 litres, 280 fewer. It is the one real gain of an ERV in an ordinary house here, and it is small next to what it costs in winter. Recovery runs all year; the bypass opens only for free cooling, when it is below 18 °C outside and above 22 °C inside.

    Frost protection

    In an HRV the moisture of the extract air can freeze in the exchanger when it is cold outside. PHI counts a pre-heater switching on below −1.5 °C for an HRV and below −8 °C for an ERV. Bucharest has 482 hours a year below −1.5 °C and 64 below −8 °C, so 67 kWh of electricity a year for the HRV and 14 kWh for the ERV. In Brașov, 205 kWh for the HRV. Units that protect themselves by unbalancing the flows are counted the same way, as a simplification.

    The unit · efficiency · PHI requirements

    The ventilation unit: efficiency, supply air, requirements

    What 90 % heat recovery efficiency means (PHI method)

    The heat recovery efficiency says how much of the extract air's heat reaches the fresh air. The PHI method measures it at the boundary of the unit and subtracts the fan heat and casing losses, so it usually comes out a few points below the brochure figure (EN 308 or EN 13141-7). The PHI-certified units in the list range from 79 to 94 %. With 90 %, of 2,942 kWh only 294 kWh remain to be covered.

    Supply air temperature at −15 °C

    At Bucharest's design temperature (−15 °C, SR 1907-1), fresh air leaves the Zehnder ComfoAir Q350 HRV at 16.9 °C with 20 °C indoors, as in the PHI test (−15 + 91 % × 35), and at 19.6 °C with 23 °C indoors. PHI asks for at least 16.5 °C so the air does not feel cold; an 80 % unit would give only 13.0 °C without a pre-heater.

    Passive House requirements for the ventilation unit

    Heat recovery efficiency at least 75 % (PHI method); fan power at most 0.45 Wh per m³ of air; supply air at least 16.5 °C; noise at most 25 dB(A) in living rooms and 35 dB(A) in the plant room; F7 (ePM1 50 %) filters on the outdoor air and G4 on the extract air; airtightness and balance of the unit, hygiene, frost protection and occupant control are also checked at certification.

    The 31 units in the calculator, with the PHI database figures checked on 31 October 2026 (Orcon: manufacturer's figures). 27 of them cover the 120 m³/h nominal flow of the 150 m² house.

    UnitTypeFlow, m³/hηHRWh/m³MoistureSource
    Zehnder ComfoAir Q350 HRVHRV70–27091 %0.24—PHI 0956vs03
    Zehnder ComfoAir Q350 ERVERV70–27092 %0.2578 %PHI 1006vs03
    Zehnder ComfoAir Q450 HRVHRV70–34588 %0.21—PHI 0954vs03
    Zehnder ComfoAir Q450 ERVERV70–34590 %0.2575 %PHI 1007vs03
    Brink Flair 325HRV69–25191 %0.21—PHI 1288vs03
    Brink Flair 325 EnthalpieERV70–24986 %0.2177 %PHI 1287vs03
    Brink Flair 400HRV70–31389 %0.20—PHI 1362vs03
    Brink Flair 400 EnthalpieERV73–31684 %0.2071 %PHI 1363vs03
    Bosch V5001C 260 (Buderus Logavent HRV176-260)HRV71–20093 %0.28—PHI 1815vs03
    Bosch V5001C 260 E (Buderus Logavent HRV176-260 E)ERV71–20084 %0.2874 %PHI 1816vs03
    Bosch V5001C 450 (Buderus Logavent HRV176-450)HRV86–34690 %0.27—PHI 1813vs03
    Bosch V5001C 450 E (Buderus Logavent HRV176-450 E)ERV86–34679 %0.2669 %PHI 1814vs03
    Blauberg Komfort EC SB350 S11 (Vents VUT 350 VB EC (0921vs03))HRV54–27979 %0.27—PHI 0812vs03
    Panasonic P-VEN20XQAZE5HRV60–15485 %0.37—PHI 2646vs03
    Panasonic P-VEN30XQAVE5HRV130–20884 %0.37—PHI 2653vs03
    Panasonic P-VEN35XQAHE5HRV80–27084 %0.35—PHI 2650vs03
    Panasonic P-VEN40XQAVE5HRV186–28485 %0.33—PHI 2654vs03
    Salda SMARTY 3X PHRV104–24885 %0.31—PHI 0810vs03
    Salda SMARTY 3X P 1.1 EERV104–26284 %0.3067 %PHI 2359vs03
    Salda SMARTY 3X VHRV107–27181 %0.30—PHI 0943vs03
    Salda SMARTY 3X V 1.1 EERV107–28682 %0.3077 %PHI 2357vs03
    Dantherm HCV400-P1HRV80–19092 %0.35—PHI 1444vs03
    Dantherm HCV460-P2HRV106–27087 %0.34—PHI 1704vs03
    Dantherm RCV320-P1HRV71–16294 %0.33—PHI 1984vs03
    Dantherm HCH 8HRV135–34083 %0.26—PHI 0273vs03
    Valsir Ariosa HV 250 SHRV65–18488 %0.33—PHI 2263vs03
    Valsir Ariosa HV 250 EERV80–18888 %0.3263 %PHI 2264vs03
    Valsir Ariosa HV 330 SHRV64–24485 %0.34—PHI 2484vs03
    Valsir Ariosa HV 330 EERV64–25388 %0.3670 %PHI 2485vs03
    Orcon HRC-350 EcoMaxHRV100–35090 %0.24—manufacturer, EN 13141-7
    Orcon HRC-450 EcoMaxHRV150–45089 %0.25—manufacturer, EN 13141-7
    Cost · payback

    What it costs and how long it takes to pay back

    How much does heat recovery ventilation cost?

    For a new 150 m² house in Romania, in October 2026, the calculation starts from 6,540 € incl. VAT: the unit 2,620 € (certified units cost about 1,700–5,300 €), ducts with manifolds, valves and silencers 2,240 €, installation with design and commissioning 1,680 €. Market guides give 4,700–6,500 € for a new house and 6,000–8,400 € in a retrofit. The gas saving, 114 € a year, pays the cost back in 57 years; with a heat pump, later. Heat recovery ventilation is not done for payback but for clean air in every room, day and night, without draughts or outside noise, without mould and without open windows in winter; the payback is here because people ask.

    Other cities · same house, same unit

    Heat recovery ventilation in nine Romanian cities

    The 150 m² house, 120 m³/h, Zehnder ComfoAir Q350 HRV (HRV) and Zehnder ComfoAir Q350 ERV (ERV), gas heating. Cold cities keep more heat, but the frost pre-heater runs longer. In no city does the ERV save more than the HRV.

    CityDesign T, °CGt, kKhSaving HRV · ERVFrost hours HRV · ERVJanuary RH HRV · ERVSummer condensate HRV · ERV, l
    Bucharest−1574.3114 · 90 €482 · 6434 % RH · 55 % RH1,325 · 1,045
    Cluj-Napoca−18104.4176 · 156 €1,083 · 14229 % RH · 55 % RH369 · 273
    Timișoara−1575.2118 · 83 €480 · 6932 % RH · 55 % RH1,523 · 903
    Iași−1889.5128 · 108 €888 · 26831 % RH · 55 % RH1,020 · 793
    Brașov−21108.2168 · 161 €1,280 · 28528 % RH · 55 % RH528 · 499
    Constanța−1268.6104 · 68 €401 · 1834 % RH · 55 % RH1,803 · 1,150
    Sibiu−18103.0155 · 132 €989 · 30029 % RH · 55 % RH715 · 540
    Craiova−1576.1121 · 97 €544 · 2833 % RH · 55 % RH1,229 · 1,216
    Cornu de Jos, Prahova−1892.7147 · 121 €832 · 16530 % RH · 55 % RH1,172 · 826
    Standards · Romania

    Dwelling ventilation in the Romanian standard

    Standard I5-2022 and dwelling ventilation

    The Romanian ventilation standard I5-2022 requires balanced (supply and extract) systems in dwellings to have heat recovery (6.1.2 (3)), a bypass or control against summer overheating, and frost to be dealt with. For extract-only ventilation it gives room flows (kitchen 75–135 m³/h depending on the number of rooms, bathroom and WC 15–30 m³/h), meant for leaky houses rather than airtight ones. It sets no minimum efficiency; the Passive House criteria (75 %, 0.45 Wh/m³, 16.5 °C) are the ones used here.

    Frequently asked questions

    Heat recovery ventilation, in short

    How many m³/h of air does a 150 m² house need?

    With 4 persons and 2.50 m ceilings: 120 m³/h, the larger of 4 × 30 = 120 m³/h (fresh air for the people) and 0.30 × 375 m³ = 112.5 m³/h (the minimum air change), rounded up. That is 0.32 air changes per hour. The unit also needs a base level (92 m³/h) and a boost level (156 m³/h).

    How much heat does heat recovery ventilation save?

    In Bucharest, without recovery, the 150 m² house would lose 2,942 kWh a year through airing. A 91 % unit keeps 2,677 kWh; the fans use 252 kWh of electricity, frost protection 67 kWh. In Brașov it keeps 3,898 kWh.

    Where should the HRV unit go in a single-storey house?

    In the attic, in the middle of the house above the hall: the ducts to the rooms are short and of similar length. Outdoor air and exhaust go straight up through the roof on the north side. In a cold attic, the unit and the ducts are insulated. For a 120 m² house with 3 persons the flow is 90 m³/h.

    How far apart should the HRV intake and exhaust be?

    At least 3 m, so exhaust air is not drawn back in; in the 120 m² example the roof terminals are 3.2 m apart. Both outdoor ducts are kept as short as possible, straight up from the unit, because they carry cold air through the warm part of the house.

    Should I choose an HRV or an ERV?

    An HRV if the house produces a lot of moisture for its volume (large family, small house) or if you want the simplest unit; an ERV if the air gets too dry in winter (few people, large house, very cold climate). For the 150 m² house with 4 persons in Bucharest, the balance gives 34 % RH in January with an HRV, already above the 30 % RH floor; an ERV would have to raise its flow to stay below 55 % RH and saves 90 € a year, against 114 € for the HRV.

    Why is the air dry in winter in a house with ventilation?

    Because cold outdoor air holds little water; warmed to 23 °C its relative humidity falls to about 20 % RH. If the flow is higher than needed, the moisture produced indoors is not enough. PHI recommends lowering the flow towards 20 m³/h per person first; only then an ERV or a humidifier.

    How much electricity does heat recovery ventilation use?

    The Zehnder ComfoAir Q350 HRV uses 0.24 Wh per m³ of air; at 120 m³/h, day and night, that is 252 kWh a year, 59 € at 0.234 €/kWh. PHI allows at most 0.45 Wh/m³.

    How much does a heat recovery ventilation system cost?

    For a new 150 m² house in Romania: 4,700–6,500 € incl. VAT for the complete system (unit, ducts, installation, commissioning); the calculator starts from 6,540 €. In a retrofit, 6,000–8,400 €.

    How long does heat recovery ventilation take to pay back?

    With gas heating the net saving in Bucharest is 114 € a year, so 57 years for 6,540 €. With direct electric heating the saving is several times larger. The reason for ventilation, though, is clean and healthy air, not payback.

    What does “PHI-certified” mean for a ventilation unit?

    That the Passive House Institute has measured the unit with its own method: heat recovery efficiency, fan power, airtightness, noise and frost protection, and published them in its component database. The figures are comparable with each other, unlike brochure figures.

    Method · updated on

    Method and sources

    The air-flow sheet follows the PHI design protocol for ventilation (the one in PHPP). Energy and humidity are steady-state balances with the hourly PVGIS climate of each city.

    1. Air flows

      Nominal flow = max(persons × 30, 0.30 × volume), rounded up to 10 m³/h. Supply by weights (living room 2, bedroom, office 1), extract by the PHI starting values, both in steps of 5 m³/h, balanced exactly. Base = nominal ÷ 1.3, boost = nominal × 1.3.

      Source: PHI protocol · Passipedia

    2. Heat

      Loss without recovery = 0.33 Wh/(m³·K) × flow × Gt, with Gt the hourly sum of the difference to 23 °C on the days with a mean below 12 °C (PVGIS typical year). Heat kept = ηHR (PHI) × loss.

      Source: PHI efficiency ratio · PVGIS

    3. Electricity

      Fans: specific power × flow × 8,760 h. Frost: electric pre-heater, 0.33 × flow × the hourly sum below −1.5 °C (HRV) or −8 °C (ERV), the PHI switch-on points.

      Source: PHI · RenewAire

    4. Humidity and cost

      xin = xout + G / (1.2 × flow × (1 − ηx)), monthly, at 23 °C in the heating months (mean below 12 °C); in summer (mean above 18 °C) the air conditioning holds 24 °C and 50 % RH and condenses G + 1.2 × flow × (1 − ηx) × (xout − xin); bypass open in between. Saving = heat kept × price of useful heat − electricity × its price; payback = cost ÷ saving.

      Source: Passipedia · Onninen

    Checks

    CheckReferenceCalculator
    Mogoșoaia sheet (PHPP): 2 persons, 413 m³130 m³/h · 0.31 h⁻¹130 m³/h · 0.31 h⁻¹
    PHI example: 504.5 m³, nominal 180base 138 · boost 234base 138 · boost 234
    Passipedia: 330 g/h, 120 m³/h, −5 °C / 90 % RH33.5 % RH32.1 % RH

    Limitations

    • Simplified steady-state balances after PHI: no pressure losses, no noise, no duct sizing.
    • Humidity is a monthly mean without material buffering, window airing or condensation. The ERV controls its flow so the extract air stays at or below 55 % RH (PHI), up to the unit’s maximum flow. Recovery runs all year; the bypass opens only for cooling (below 18 °C outside, above 22 °C inside). In summer the water condensed by the air conditioning is counted, not the cooling energy; the summer moisture recovery is taken equal to the winter one.
    • The frost pre-heater is counted as electric at the PHI switch-on points; flow unbalancing is treated the same way.
    • Prices are guides (October 2026), not quotes.

    Sources

    Calculation and text: SEMPER SUPRA INITIATIVE S.R.L. · Climate data: PVGIS © European Union, 2001–2026 · Units: PHI database, 31 October 2026 · Prices: October 2026, 1 € = 5.3495 lei (BNR).