Roof U-value and R′ calculator
For the three roofs found on Romanian houses: the mansard with mineral wool between and under the rafters, the unheated attic with insulation on the floor slab, and the reinforced-concrete flat roof. The calculation shows heat loss including the rafters and battens (EN ISO 6946), the temperature through the layers, condensation month by month and summer behaviour. Choose the roof type, then drag the insulation in the drawing or move the sliders.
—
—
Drag the orange marker along the scale: the insulation thickness adjusts to reach the U you pick.
PHI: Passive House Institute, cool-temperate zone · nZEB: Mc 001-2022, new residential buildings (R′ 6.67) · renovation: Mc 001-2022, major renovation (R′ 5.00) · Order 2017: Order 2641/2017 (R′ 5.00). For roofs the values coincide in pairs. Recommended values, shown for comparison.
—
Moisture and heat through the roof
Condensation is calculated month by month with the average climate of the chosen city. Summer behaviour is calculated for a day with a sinusoidal outdoor temperature.
—
The calculation describes the roof away from its edges: thermal bridges at the eaves, ridge, parapet, roof windows or chimneys are not included and are calculated separately. Condensation is estimated by vapour diffusion (ISO 13788), without air leaking through gaps, which in mansards often brings more water than diffusion. It is not a design calculation.
Common Romanian roofs, compared
An old mansard with 16 cm of wool between the rafters, board sheathing and bitumen felt has U′ 0.284 W/(m²K) and, without a vapour control layer, collects 4,307 g/m² of condensate in Bucharest. The build-up recommended by manufacturers, 18 cm between and 5 cm under the rafters, reaches U′ 0.175; with 10 cm under the rafters it drops below 0.15 (0.143). The attic with 30 cm of wool and the flat roof with 20 cm of polystyrene reach 0.138 and 0.162. Click a roof to open it in the calculator.
| Roof | U′ W/(m²K) | R′ m²K/W | Time shift | Condensation, Bucharest |
|---|---|---|---|---|
| Mansard | ||||
| 0.284 | 3.52 | 1.8 h | 4,307 g/m² | |
| 0.230 | 4.35 | 1.2 h | no | |
| 0.175 | 5.71 | 1.6 h | no | |
| 0.143 | 6.99 | 2.1 h | no | |
| 0.125 | 8.01 | 2.9 h | no | |
| 0.146 | 6.84 | 9.9 h | no | |
| Unheated attic | ||||
| 0.202 | 4.96 | 6.1 h | no | |
| 0.138 | 7.23 | 6.7 h | no | |
| 0.167 | 5.98 | 8.1 h | 13 g/m² | |
| Flat roof | ||||
| 0.324 | 3.09 | 7.7 h | no | |
| 0.162 | 6.19 | 9.3 h | no | |
| 0.131 | 7.66 | 10.4 h | no | |
| 0.184 | 5.44 | 13.7 h | no | |
Mansard: rafters 8 × 18 cm at 80 cm (16 cm for the old mansard), 5 cm battens at 60 cm under the rafters, vapour-open underlay over the rafters, vapour control layer sd 2 m, 12.5 mm plasterboard. Attic: 13 cm reinforced-concrete slab, tiles on felt above (Ru 0.2), no vapour control layer. Flat roof: 15 cm slab, 5 cm screed to falls, aluminium-faced bitumen vapour barrier, bitumen waterproofing. Indoor humidity class 3 (ISO 13788).
How much insulation for the reference values
The thickness, rounded up to the centimetre, at which the roof reaches U′ 0.20 W/(m²K) (Mc 001-2022 for renovation and Order 2641/2017, R′ 5.00) and U′ 0.15 W/(m²K) (Mc 001-2022 for new residential nZEB buildings, R′ 6.67, the same value as the Passive House Institute).
| Material | U′ 0.20 | U′ 0.15 |
|---|---|---|
| Mansard · wool under the rafters (rafters 8 × 18 cm at 80 cm, filled with the same material) | ||
| Unifit 032 · Knauf glass wool λ 0.032 | 2 cm | 7 cm |
| Unifit 035 · Knauf glass wool λ 0.035 | 3 cm | 9 cm |
| Unifit 039 · Knauf glass wool λ 0.039 | 4 cm | 12 cm |
| Classic 044 · Knauf glass wool λ 0.044 | 7 cm | 15 cm |
| Airrock ND · Rockwool stone wool λ 0.035 | 3 cm | 9 cm |
| Steico flex 036 · wood fibre λ 0.036 | 3 cm | 10 cm |
| Unheated attic · on the 13 cm slab | ||
| Unifit 032 · Knauf glass wool λ 0.032 | 15 cm | 21 cm |
| Unifit 035 · Knauf glass wool λ 0.035 | 17 cm | 22 cm |
| Unifit 039 · Knauf glass wool λ 0.039 | 18 cm | 25 cm |
| Classic 044 · Knauf glass wool λ 0.044 | 21 cm | 28 cm |
| Airrock ND · Rockwool stone wool λ 0.035 | 17 cm | 22 cm |
| Steico flex 036 · wood fibre λ 0.036 | 17 cm | 23 cm |
| EPS A100 · Austrotherm expanded polystyrene λ 0.036 | 17 cm | 23 cm |
| Flat roof · on the 15 cm slab | ||
| EPS A100 · Austrotherm expanded polystyrene λ 0.036 | 17 cm | 23 cm |
| EPS A150 · Austrotherm expanded polystyrene λ 0.034 | 16 cm | 22 cm |
| XPS TOP 30 · Austrotherm extruded polystyrene λ 0.035 | 17 cm | 23 cm |
| Rigid stone wool roof boards λ 0.039 | 19 cm | 25 cm |
For the mansard, the thickness is the layer under the rafters, on top of the 18 cm between them. The reference values are recommendations, not requirements.
The roof, the wool and moisture
How much wool does a mansard need for nZEB?
Mc 001-2022 recommends R′ ≥ 6.67 m²K/W for the roofs of new residential nZEB buildings, i.e. U′ ≤ 0.15 W/(m²K). For a mansard with 8 × 18 cm rafters at 80 cm filled with Unifit 035, at least 9 cm more wool is needed under the rafters; for renovation (U′ 0.20), 3 cm is enough. The usual 18 + 5 cm build-up has U′ 0.175. For an attic, the same value takes 28 cm of Classic 044 wool on the slab, and for a flat roof 22 cm of EPS A150.
Why does a mansard get hot in summer?
Glass wool is very light, so it lets the day's heat wave through almost undamped: for a mansard with 18 + 10 cm of Unifit 035, the layers under the ventilated gap have a time shift of 2.1 hours and a decrement factor of 0.96. With wood fibre of the same thickness, the time shift rises to 9.9 hours and the decrement falls to 0.35. The tile colour matters too: for 120 m² in Bucharest, the heat entering through the roof in the hot season is 229 kWh with red clay tiles and 327 kWh with anthracite clay tiles. Roof windows and night ventilation often matter more than the opaque roof.
Does a mansard need a vapour control layer?
It depends on the layer over the rafters. In Brașov, with normal indoor humidity, a vapour-open underlay laid directly on the rafters (sd 0.02 m) gives no condensation even without a vapour control layer. With board sheathing (sd ≈ 1.2 m) and no vapour control, 6,083 g/m² builds up, which does not dry out within a year; with an sd 2 m membrane, 379 g/m², dry by June. With bitumen felt on the boards (sd of tens of metres), the 2 m membrane leaves 1,230 g/m², does not dry out within a year, and a 100 m polyethylene barrier 13 g/m², dry by July. The rule: the outer layers must be more vapour-open than the inner ones. Airtightness matters just as much, because warm air escaping through gaps carries more water than diffusion.
How much do the rafters matter?
Timber (λ 0.13) conducts heat almost four times better than wool. With 18 cm of wool only between 8 cm rafters at 80 cm (10 % timber), U′ is 0.230, against 0.185 without timber: 24 % more. With 10 cm rafters at 60 cm, U′ rises to 0.260. A 5 cm layer under the rafters covers the timber and cuts the difference to 20 % (U′ 0.175). The calculation follows the EN ISO 6946 combined method, the mean of the upper and lower limits.
Do the tiles and the ventilated gap insulate the roof?
No. Under EN ISO 6946, a well-ventilated air layer (openings of at least 1500 mm² per metre) and everything above it are left out of U; the outer face of the underlay is treated as a surface in still air, with the same resistance as inside (0.10 m²K/W). The tiles and the ventilated gap protect against rain and sun and help the roof dry out, but they add no thermal insulation.
Walkable attic: what happens with an OSB walkway over the wool?
With 25 cm of Unifit 039 on the slab, U′ is 0.147. With 5 cm joists at 60 cm and an 18 mm OSB walkway, U′ rises to 0.167. The OSB (μ ≈ 200, sd ≈ 3.6 m) sits on the cold side of the wool, so vapour can stop under it: in Brașov the calculation gives 16 g/m², dry by April; with an sd 2 m membrane on the slab, 5 g/m², dry by March.
Flat roof: polystyrene or stone wool?
At 20 cm, EPS A150 polystyrene (λ 0.034) gives U′ 0.162 and rigid stone-wool roof boards (λ 0.039) 0.184. Both sit under the bitumen waterproofing (sd ≈ 400 m), whose underside stays close to the outdoor temperature however thick the insulation is. So condensation depends on the vapour barrier, not on thickness: with an aluminium-faced bitumen vapour barrier (sd ≈ 1500 m), the calculation for Bucharest gives no condensation; with a plain bitumen barrier (sd ≈ 200 m), 5 g/m², dry by June (in Brașov, 8 g/m², does not dry out within a year); without a barrier, 47 g/m², dry by July for polystyrene and 80 g/m², dry by August for stone wool. Stone wool is non-combustible (A1) and, being heavier, delays summer heat longer (time shift 13.7 h against 9.3 h).
How much heat does a house roof lose in a year?
For 120 m² of roof in Bucharest (2005–2023 typical meteorological year, 172 days averaging 12 °C or less, 2,579 degree-days): the old mansard with 16 cm of wool loses about 2,107 kWh in the cold season, the mansard with 18 + 10 cm 1,062 kWh, the attic with 30 cm of Classic 044 1,027 kWh, and the flat roof with 20 cm of polystyrene 1,200 kWh. In summer more heat enters through the roof than through the walls, because the sun is almost overhead: 229 kWh for the mansard with red tiles, 401 kWh for the flat roof with black bitumen and 111 kWh for the same flat roof with a white membrane.
How the calculation works
The calculator follows EN ISO 6946 for U, with the combined method for layers crossed by timber, EN ISO 13788 for condensation and the inner surface, and EN ISO 13786 for summer. The combined method reproduces exactly the worked example published by the Scottish Government.
Layers, rafters and battens
Where the wool is crossed by timber, U is the mean of the upper limit (wool and timber strips in parallel) and the lower limit (each layer homogenised, layers in series). Rafters with battens across them give four strips. No air-gap correction (level 0): the rolls are cut 2 cm wider and fitted tight, and the second layer covers the joints of the first.
Source: EN ISO 6946:2017 · worked example
Ventilated gap and attic
For the mansard, the ventilated gap under the tiles and everything above it are left out of U, and the outer face has Rse equal to Rsi (0.10). For the attic, the ventilated space and the roof count as one resistance Ru. Heat flows upwards: Rsi 0.10.
Source: EN ISO 6946:2017
Temperature through the roof
Temperature falls in proportion to each layer's resistance, separately through the wool and through the timber, from 20 °C inside to the design outdoor temperature of the climate zone.
Source: SR 1907-1 design temperatures
Condensation month by month
For each month, in daily steps, the vapour pressure is compared with the saturation pressure at every interface. Condensate builds up and evaporates over time; the less favourable path, through the wool or through the timber, is reported.
Source: EN ISO 13788:2012
Summer
The EN ISO 13786 matrix method for a 24-hour period gives the time shift, decrement factor and internal heat capacity. For the mansard, the layers under the ventilated gap are used.
Source: EN ISO 13786:2017 · reference case
The whole year
The city's PVGIS typical meteorological year, day by day: heating to 20 °C on days averaging 12 °C or less, and in summer the sun on the covering (horizontal radiation × absorptance × Rse 0.04) is added to the air temperature.
Source: PVGIS
Checks
| Check | Reference | Calculator |
|---|---|---|
| EN ISO 6946, example 6.B.2: upper limit | 3.435 | 3.435 |
| lower limit | 3.304 | 3.304 |
| U | 0.30 | 0.297 |
| ubakus.de: 18 cm of 035 wool between 8 cm rafters at 80 cm | 0.229 | 0.230 |
| ubakus.de, Zwischensparrendämmung example | 0.191 | 0.193 |
| EN ISO 13786, 20 cm concrete: |Y₁₂| | 1.83 W/(m²K) | 1.827 |
| EN ISO 13786: Y₁₂ time shift | −5.68 h | -5.68 h |
Limitations
- Thermal bridges at the eaves, ridge, parapet, roof windows and chimneys are not included.
- Air leaking through gaps is not calculated; in mansards it can bring more water than diffusion.
- Humidity-variable membranes and the inverted flat roof (extruded polystyrene over the waterproofing) are not modelled.
- In summer, the roof's slope and orientation are approximated by the horizontal radiation.
- λ is the declared dry value; the μ and sd values are typical.
- For Timișoara and Prahova the climate zone is not confirmed in the sources checked.
- Mc 001-2022 and Passive House values are shown as references, not as a verdict on the roof.
Sources
- EN ISO 6946:2017, thermal resistance and transmittance
- EN ISO 13788:2012, condensation and inner surface
- EN ISO 13786:2017, dynamic thermal characteristics
- Passive House Institute, criteria for opaque construction systems
- Mc 001-2022, minimum thermal resistances (summary, Romanian)
- Order 2641/2017, table 1 (Romanian)
- Scottish Government, combined-method worked examples
- Knauf Insulation Romania, mansard insulation (Romanian)
- Austrotherm Romania, EPS data (Romanian)
- PVGIS, climate of the cities
Calculation and text: SEMPER SUPRA INITIATIVE S.R.L. · Climate data: PVGIS © European Union, 2001–2026.